A control valve is a valve with a motor on it: an actuator that moves the stem on command, and usually a positioner that makes sure the stem went where it was told. The body is in Valves.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Pneumatic signal | 3–15 psi (0.2–1.0 bar) · 9 psi = 50 % |
| Electric signal | 4–20 mA · 12 mA = 50 % |
| I/P converter supply | about 20 psi (1.4 bar), regulated and filtered |
| Positioner supply, spring-and-diaphragm | 20–50 psi (1.4–3.5 bar) by bench set; at the actuator plate value |
| Positioner supply, piston actuator | 60–100 psi (4–7 bar); at the plate value |
| Bench set | 3–15 psi common; 6–30 psi where more seat load is needed |
| Signal vs stem position | within about 1–2 % of stroke at 0, 25, 50, 75, 100 %, both directions |
| Remote tank valve stroke time | a few seconds to about a minute by size; slower than last month is the reading |
| Electric actuator torque switch | trips at the seat, never mid-travel |
| Filter-regulator bowl | dry; water here is a dryer problem (see Compressed Air, Stop 7) |
| Hydraulic power unit | at the plate pressure; standby pump stopped; tank level steady |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Stem doesn't follow signal; positioner output pinned at supply | Stem by handwheel; feedback arm | Stem stuck — packing over-tight, scale, varnish; arm off or slipped | Free the stem; refit and pin the arm |
| Follows the signal, slowly | Exhaust silencer; supply gauge during a stroke | Silencer blocked; filter element loaded; tubing kinked or wet | Clean or change silencer and element; blow the line |
| Temperature hunting, stem cycling | Controller to manual at fixed output | Stem stops: tuning or sensor lag. Stem still cycles: stiction or positioner gain | Free the stem first; tune last |
| Process hunting, stem steady | What else is cycling | Another loop interacting — HT with LT, heater with viscosity; load swinging | Fix the other loop; don't detune this one |
| Signal 50 %, stem at 70 % | Zero and span at 0 and 100 % | Calibration drifted; feedback linkage slipped; wrong cam fitted | Zero, then span, then mid-points |
| Supply gauge dips when the valve strokes | Filter-regulator element and bowl | Element blocked; water in the small-bore line | Drain; change element; blow the line |
| I/P output stuck at 3 psi, loop current normal | I/P supply; nozzle | Nozzle blocked with rust or water; supply port blocked | Clean per maker or change the I/P |
| Remote tank valve won't move from the mimic | Solenoid click; air or oil at the actuator | Wet air varnished the bore; spool stuck; coupling sheared | Cycle it a few times; manual override; strip and clean |
| Remote valve moves, indicator doesn't | Limit switch or potentiometer at the actuator | Cam slipped; switch failed; wire off | Reset cam; renew switch |
| Hydraulic remote valve creeps on its own | Cylinder seals; the block | Piston seal passing; spool leaking | Blocking plate and tag; renew seals |
| Hydraulic power unit cycling often, standby starting | Oil on deck; accumulator | External leak; precharge lost; relief weeping | Find the leak; recharge; set relief |
| Electric actuator torque trip mid-travel | Handwheel feel after declutch | Stiff or scaled valve; obstruction; packing too tight; torque set low | Free the valve; set torque per maker — not just higher |
| Electric actuator runs, stem doesn't move | Stem nut; coupling | Stripped stem nut; sheared key | Renew stem nut |
| Wax-element valve runs hot, settles slowly | Pipe temperatures at each port by hand | Element tired; sleeve scaled | Renew element; descale |
| Valve went the wrong way on loss of air | Fail position on the drawing | Lock-up valve stuck; actuator reassembled the other way after overhaul | Confirm fail position after any actuator work |
Draft: this page is drawn from the book manuscript and is still being checked.