Part II · The Equipment · Family 4 · Control It · Stage 3 · First hitch

Control Valves, Actuators, and Positioners

A control valve is a valve with a motor on it: an actuator that moves the stem on command, and usually a positioner that makes sure the stem went where it was told. The body is in Valves.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Pneumatic signal3–15 psi (0.2–1.0 bar) · 9 psi = 50 %
Electric signal4–20 mA · 12 mA = 50 %
I/P converter supplyabout 20 psi (1.4 bar), regulated and filtered
Positioner supply, spring-and-diaphragm20–50 psi (1.4–3.5 bar) by bench set; at the actuator plate value
Positioner supply, piston actuator60–100 psi (4–7 bar); at the plate value
Bench set3–15 psi common; 6–30 psi where more seat load is needed
Signal vs stem positionwithin about 1–2 % of stroke at 0, 25, 50, 75, 100 %, both directions
Remote tank valve stroke timea few seconds to about a minute by size; slower than last month is the reading
Electric actuator torque switchtrips at the seat, never mid-travel
Filter-regulator bowldry; water here is a dryer problem (see Compressed Air, Stop 7)
Hydraulic power unitat the plate pressure; standby pump stopped; tank level steady

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Stem doesn't follow signal; positioner output pinned at supplyStem by handwheel; feedback armStem stuck — packing over-tight, scale, varnish; arm off or slippedFree the stem; refit and pin the arm
Follows the signal, slowlyExhaust silencer; supply gauge during a strokeSilencer blocked; filter element loaded; tubing kinked or wetClean or change silencer and element; blow the line
Temperature hunting, stem cyclingController to manual at fixed outputStem stops: tuning or sensor lag. Stem still cycles: stiction or positioner gainFree the stem first; tune last
Process hunting, stem steadyWhat else is cyclingAnother loop interacting — HT with LT, heater with viscosity; load swingingFix the other loop; don't detune this one
Signal 50 %, stem at 70 %Zero and span at 0 and 100 %Calibration drifted; feedback linkage slipped; wrong cam fittedZero, then span, then mid-points
Supply gauge dips when the valve strokesFilter-regulator element and bowlElement blocked; water in the small-bore lineDrain; change element; blow the line
I/P output stuck at 3 psi, loop current normalI/P supply; nozzleNozzle blocked with rust or water; supply port blockedClean per maker or change the I/P
Remote tank valve won't move from the mimicSolenoid click; air or oil at the actuatorWet air varnished the bore; spool stuck; coupling shearedCycle it a few times; manual override; strip and clean
Remote valve moves, indicator doesn'tLimit switch or potentiometer at the actuatorCam slipped; switch failed; wire offReset cam; renew switch
Hydraulic remote valve creeps on its ownCylinder seals; the blockPiston seal passing; spool leakingBlocking plate and tag; renew seals
Hydraulic power unit cycling often, standby startingOil on deck; accumulatorExternal leak; precharge lost; relief weepingFind the leak; recharge; set relief
Electric actuator torque trip mid-travelHandwheel feel after declutchStiff or scaled valve; obstruction; packing too tight; torque set lowFree the valve; set torque per maker — not just higher
Electric actuator runs, stem doesn't moveStem nut; couplingStripped stem nut; sheared keyRenew stem nut
Wax-element valve runs hot, settles slowlyPipe temperatures at each port by handElement tired; sleeve scaledRenew element; descale
Valve went the wrong way on loss of airFail position on the drawingLock-up valve stuck; actuator reassembled the other way after overhaulConfirm fail position after any actuator work

Draft: this page is drawn from the book manuscript and is still being checked.