A boiler turns feedwater into steam by burning oil in a furnace or by catching heat from engine exhaust. The burner, the water level, and the fire side are what fail; the plant around them is in Steam.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Flue gas O₂ / CO₂, oil firing at high fire | 3–5 % / 12–14 % |
| Smoke | Light haze at most; Bacharach 1–2 |
| Stack temperature, fire-tube aux boiler | steam temperature + 50–100 °C |
| Clean the fire side at | stack 30–50 °C above clean baseline at the same firing rate |
| Fuel viscosity at the atomizer — pressure jet / rotary cup | 12–18 cSt / up to about 25 cSt |
| Atomizing steam or air, assisted burners | 2–5 bar |
| Turndown — simplex jet / spill-return or assisted / rotary cup | ~2:1 / up to ~10:1 / ~8–10:1 |
| Flame signal | Steady, well above the maker's minimum |
| EGB circulation ratio (water pumped ÷ steam made) | 3–8 |
| EGB gas-side ΔP, blow or wash at | about 1.5× clean baseline |
| Casing by hand or IR gun | Under 60–70 °C |
| Thermal oil outlet | 180–300 °C by system |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Lockout in pre-purge | Air switch; damper limit switches | Fan belt or motor; linkage slipped; switch tube blocked | Prove the fan; reset the linkage |
| Lockout at trial, no flame seen | Electrodes; tip | Cracked insulator or wrong gap; tip coked; fuel cold; air in the line | Clean and gap; change the tip; bleed |
| Lockout at trial, flame was there | Scanner lens; aim | Dirty lens; mis-aimed after work; scanner failing | Clean; re-aim; replace |
| Flame failure in run | Fuel pressure and temperature trend | Pressure dips — changeover, filters, pump wear; water in fuel | Change filters; drain the settler; hold viscosity |
| Black smoke | Fuel temperature; damper | Cold fuel; too little air; worn tip or dirty cup | Fuel temperature first, then air, then atomizer |
| Clear stack, high O₂ | Linkage; fuel pressure | Too much air; fuel pressure low | Reset the ratio; check the regulator |
| Pulsating or rumbling flame | Atomizing and fuel pressure | Unstable atomization; air leaks into the furnace; damper hunting | Steady the pressures; seal the leaks |
| Flame on the rear wall | Quarl; tip part number | Worn quarl; cold fuel; wrong tip | Right tip; fuel to spec; renew quarl |
| Stack temperature up, same firing rate | Fire-side ports | Soot; water-side scale; baffle burnt out | Clean; test the water; inspect baffles |
| Casing hot spot, blistered paint | Wall behind it through the port | Refractory fallen; insulation displaced; gas past a door | Fire-side opening soon |
| Level cycling wide, pump short-cycling | Probe column or float chamber | Sludge on probes or float; band too narrow; swell | Blow down the column; widen the band |
| Safety valve feathering below set | Working pressure vs set | Dirt on the seat; working pressure too close; spring relaxed | Lift on the easing gear; persists — survey job |
| EGB ΔP up, blowing logged daily | Header drain at the next blow | Wet steam; nozzles blocked; soot baked on during low circulation | Drain to dry steam; wash at the next stop |
| Thermal oil outlet climbing, flow low | Pump; strainer; expansion tank | Pump failing; strainer blocking; vapor in the coil | Burner off until flow is proven |