ETO · Part 1 · Theory, and Part 4 · Motors

Variable Frequency Drive

A drive turns the ship’s 60 Hz into whatever frequency the motor needs: rectify it to DC, then chop the DC back into AC. See how it does that, what it does to the rest of the bus, how to set one up, and how to read its trips.

Pulse-width modulation, one output cycle

The three stages

Rectifier. Six diodes turn 440 V three-phase into DC. The capacitors charge to the peak of the line voltage: 440 × √2 ≈ 620 V with no load, about 594 V running.

DC bus. Big capacitors smooth it. They hold that voltage after the drive is switched off: wait the time on the warning label (often 5 to 15 minutes) and measure the DC bus yourself before you touch anything inside.

Inverter. Six IGBTs switch each motor lead between the + and − of the bus thousands of times a second. The wider the pulse, the more voltage. Vary the pattern sinusoidally and the motor’s inductance turns the pulses into a near-sine current.

Volts per hertz. To keep the motor’s magnetic flux right, voltage rises with frequency: 440 V ÷ 60 Hz = 7.3 V per Hz. Above 60 Hz the drive has no more volts to give, so torque falls off.

The real carrier is far faster than drawn: at 4 kHz there are 67 pulses in every 60 Hz cycle.