ETO · Part 1 · Theory you’ll use with a meter in your hand

Three-Phase

Three sine waves 120° apart, and the handful of facts that follow from it: why the meter reads 440 between lines and 254 to the wye point, what changes between wye and delta, and why swapping any two leads reverses a motor.

One cycle
440 V, 60 Hz system

A meter shows RMS. The insulation, and you, see the peaks.

What to take away

At any instant the three add to zero. Watch the waves: whenever one is at its peak, the other two are each at minus half. That’s why a balanced three-wire system needs no return conductor.

Line voltage is √3 times phase voltage. A–B is the difference between two phasors 120° apart: 1.732 times longer, and 30° ahead of A. 254 V × 1.732 = 440 V.

RMS × 1.414 = peak. 440 V RMS between lines peaks at about 622 V.

One cycle at 60 Hz is 16.7 ms; at 50 Hz it’s 20 ms. The phases are a third of that apart: 5.6 ms at 60 Hz.