The generator panel has five meters that tell one story: kW is the work, kVAR is the magnetizing, kVA is what the windings and breaker carry, amps follow kVA, and power factor is the ratio. Build a load and watch the triangle, then read two sets in parallel and fix what’s wrong.

DG1, 900 kW / 1,125 kVA, 440 V, 1,476 A
What the triangle tells you

kW (along the bottom) is real power: the fuel the engine burns. The governor controls it.

kVAR (straight up) is the current motors and transformers need just to magnetize their iron. It does no work, burns almost no fuel, but it flows through the windings, cables and breakers all the same. The AVR controls it.

kVA (the long side) is what the generator, breaker and cables actually carry. Amps follow kVA, not kW.

Power factor = kW ÷ kVA. Heaters and lights sit at 1.0; induction motors at full load around 0.85; a motor running unloaded still draws its full magnetizing kVAR for very little kW, so it drags the power factor right down.