ETO · Part 5 · Automation, alarms and sensors

RTD and Thermocouple

Most temperatures on board come from one of two sensors: a platinum resistance (Pt100) for water, oil and bearings, a thermocouple for exhaust. Each one fails in its own way, and each lies in its own way when it’s wired wrong.

Lube oil inlet temperature, Pt100
Wiring

Meter on the sensor

Pt100 in one page

100 Ω at 0°C, rising about 0.385 Ω per degree: 119.4 Ω at 50°C, 138.5 Ω at 100°C. Disconnect it and read it with your meter: that’s the quickest test there is.

Lead resistance adds to the reading. In a 2-wire circuit both leads are in series with the sensor: every 0.385 Ω of copper reads as one degree hot.

3-wire uses the third lead to measure and subtract the lead resistance. It works if the leads match; a bad terminal on one lead brings the error back.

4-wire feeds current down one pair and measures voltage on the other: no lead error at all.