Three short exercises with a fire and general service pump: start it the right way, see what a closed valve does to a centrifugal pump and to a positive displacement pump, and find out why a second pump doesn't double the flow.
Fire and GS pump. Pressure comes from the spinning impeller.
Gear pump, like a lube oil or fuel transfer pump. Every turn pushes the same volume out.
Close the discharge on a centrifugal pump and it just churns: pressure tops out at its shut-off head, flow goes to zero, current drops, and the water in the casing slowly heats up. Close the discharge on a positive displacement pump and the pressure keeps climbing until something gives: the relief valve, the pipe, the casing or the motor. Never start a PD pump against a closed discharge, and never gag its relief valve.
Two identical pumps in parallel give twice the flow at any one pressure: the combined curve is each pump's curve stretched sideways. But more flow through the same pipes means more friction, so the system needs more pressure, and the operating point slides up the system curve. The steeper the system curve (lots of friction), the less the second pump adds. Mostly static lift (a flat system curve) and the second pump adds more.
Pumps in parallel need similar shut-off heads. If one is worn and the main's pressure is above its shut-off head, its check valve stays shut. It runs dead-headed, churning and heating up while it adds nothing.