Most of the ship’s analog readings ride on a 4–20 mA loop: a 24 V supply, a two-wire transmitter in the field and a 250 Ω input on the alarm system card. Scale the signal, find a break with nothing but a voltmeter, then calibrate a transmitter the way the paperwork wants it.

The loop
Why 4 and not 0

Live zero. 4 mA means 0% of range. 0 mA means something is broken: a wire, a fuse, the transmitter. If 0% were 0 mA, a cut cable would read “tank empty” and nobody would know.

Power and signal on the same two wires. A two-wire transmitter runs on the few milliamps below 4, and sets the loop current to say what it measures.

The card reads volts. The 250 Ω input resistor turns 4–20 mA into 1–5 V. That’s why you can read the loop with a voltmeter across the card input without breaking anything: volts ÷ 250 = amps.

Out of range means fault. Most systems treat below about 3.6 mA or above about 21 mA as a failure (the NAMUR NE 43 convention), not a reading.

Pressure transmitter, 0 to 10 bar
AMS · LO PRESS ME INLET
Work it out