Induction Motor

Nine out of ten motors on board are three-phase squirrel-cage induction motors. Learn to read one from its speed and its amps, read its nameplate and set its overload, and catch it when it’s lost a phase.

37 kW, 4-pole, 440 V, 60 Hz
━ torque━ current- - load torque

Slip is a load gauge

The field turns at synchronous speed: 120 × 60 Hz ÷ 4 poles = 1800 rpm. The rotor always runs a little slower; that difference, the slip, is what induces the rotor current that makes torque.

Slip grows nearly in step with load. So a tachometer on a pump motor tells you roughly how hard it’s working: 1796 rpm is idling, 1770 is about full load, 1740 is overloaded.

Current tells you less than you think at light load. An unloaded motor still draws a third of its full-load amps just to magnetize itself. That’s also why its power factor is poor.

Low voltage hurts. Torque falls with the square of voltage, so at 90% volts the motor slips further and draws more current to carry the same load: it runs hotter.

Starting: 6 to 8 times full-load current until it’s near speed. Past the breakdown point the motor stalls and the current goes straight to locked-rotor value.