ETO · Part 2 · Generation

Governor Knobs

A mechanical-hydraulic governor on one of M/V Hawsepiper’s 900 kW, 900 rpm generator sets, with the four knobs you’ll actually touch. It starts out hunting. Settle it down, make it pick up a load step cleanly, and set it up to share load in parallel.

Last 30 seconds
━ frequency━ fuel rackshaded: 60 ± 0.1 Hz
The governor
Jobs to do
  • Stop the hunting. Frequency steady within about 0.15 Hz for 8 seconds.
  • Take a 25% load step cleanly. Back inside 60 ± 0.1 Hz within 6 seconds of the step, with no hunting after. (Isochronous, droop at zero.)
  • Set 3% droop for parallel running. Droop dial at 3%, speed setting so full load lands on 60 Hz.

Settling a hunting UG

With the engine at speed and light load, open the needle valve two or three turns and let it hunt for about half a minute: that bleeds trapped air out of the oil passages. Then set the compensation pointer about midway and close the needle valve slowly until the hunting just stops. Bump the load and watch it come back. Too slow, open the needle a little or reduce compensation; overshooting, the other way.

The maker gives the needle valve’s working range, usually well under a turn open. Don’t close it right down to cure hunting: it’ll look steady but take ages to come back to speed after a load change.

Before you blame the governor, look at the linkage to the fuel racks (sticky racks or worn joints hunt too) and the governor oil level and condition.

Same knobs on a Woodward 2301A
UG knob2301A, roughly
Speed settingRated speed pot, plus the raise/lower inputs from the switchboard
Speed droopDroop pot (for droop mode), or isochronous with load sharing lines between sets
Compensation pointer and needle valveGain, Reset, and Actuator Compensation pots
Load limitStart fuel limit and the actuator’s own stop

Check your control’s manual: 2301A variants differ in which pots they have.