ETO · Part 2 · Generation

Brushless Alternator

No brushes, no slip rings: a small generator on the same shaft makes the field for the big one. Follow the excitation chain, watch DG3’s AVR work harder as the load and its kVAR go up, test the rotating diodes, then find out why a set won’t hold its voltage.

DG3 · 900 kW, 440 V, 60 Hz, 0.8 pf · 1,125 kVA, 1,476 A
The chain, in order

PMG (permanent magnet generator): magnets on the shaft, coils on the frame. It makes power for the AVR from the moment the shaft turns, whatever the main output is doing.

AVR: compares the output voltage (through the sensing transformer) with its setting and feeds DC to the exciter field.

Exciter: an upside-down generator. Its field is stationary; its armature turns with the shaft and makes three-phase AC.

Rotating rectifier: six diodes on the shaft turn that AC into DC for the main field. A varistor across them soaks up voltage spikes.

Main field and stator: the spinning DC field induces 440 V in the main stator. A couple of amps in the exciter field control hundreds of amps in the main field: about a hundredfold from one end of the chain to the other.

Self-excited sets without a PMG take AVR power from their own output, so they rely on residual magnetism to start building up. Lose that and they need their field flashed.

Load on the set
Excitation
Rotating diodes