ETO · Part 3 · Switchboards and distribution

Breaker Won’t Close

A generator’s air circuit breaker that won’t close is one of the commonest calls an ETO gets, usually at a bad moment. The breaker is telling you why on its front panel. Read the flags, measure the coils, and name the reason. Then rack one out the safe way.

No.2 generator breaker, 1600 A
0 of 0

Click any part of the front panel to look at it.

Everything that has to be true to close
  • Closing springs charged. The motor (or the hand lever) winds them; the close button just releases them.
  • Undervoltage release (UVT) energized. No volts on it and the mechanism is held trip-free. The most common one.
  • Racked fully in, all the way to CONNECTED, with the racking handle out.
  • Mechanism reset after a protection trip (the trip flag pushed back in).
  • No standing trip: nothing holding the shunt trip coil energized.
  • The closing circuit made up: control power, the synchronizing check permissive, and the electrical interlocks (shore power, bus tie, other generators).

Look before you measure: the springs, position, handle and trip flag take ten seconds and need no meter.

The call

Meter and switchboard checks
    What’s stopping it?