ETO · Part 2 · Generation, and Part 3 · Distribution

Blackout Drill

Two of M/V Hawsepiper’s 900 kW diesel generators on the main board, the 250 kW emergency generator on the emergency board, and the bus tie between them. Overload one set and watch preferential trip and the standby start. Then black the ship out and follow the chain that brings the lights back, with the 45-second clock running.

One-line
Event log
seconds since the drill started
    Emergency board dead for
    0.0 s
    limit 45 s
    Make something happen
    Your hands
    The chain

    Preferential trip: when the running set is overloaded, non-essential feeders (galley, A/C, then reefers or deck gear) are tripped in stages to save the set, and the power management starts the standby.

    Blackout: the emergency board’s undervoltage relay sees the voltage go. The bus tie opens, the emergency generator starts, and its breaker closes onto the dead emergency board. It’s interlocked so it can’t close while the bus tie is closed.

    The 45 seconds: SOLAS wants the emergency generator started and connected automatically within 45 seconds. On most cargo ships, this one included, nothing covers the gap: it is a full blackout, emergency lights too, until the set closes on. Passenger ships and some newer cargo ships carry a battery for it. Meanwhile the standby main set starts and closes onto the dead main board, and essential motors restart in steps so they don’t all hit it at once.

    Back to normal: transfer the emergency board back to the main board by hand: emergency generator breaker open, bus tie closed. Then let the emergency generator run unloaded to cool down before it stops.